SAM-DT, Dr.Horn, 16.05.2011


GEAPAS 500 News DT, Dr. Horn

Date

Author

Message

16.05.2011

DT, Dr. Horn

ZKG501

ZKG500 will be replaced by ZKG501 in 08/2011. Standard-software will be 271.001100, ship-specific software will be 271.0011xy.

Software for ZKG501 is not compatible with ZKG500's software in any direction.

Therefore ZKG500 will be kept available.


New features are:

  • Voltage-control

  • Parametrisation & remote control via CAN1 / CAN2 (redundant)

  • “IDLE”-command (DG running, CB open)

  • Minimum number of generators per busbar

  • 16 GEN possible

  • ...

09.11.2010

DT, Dr. Horn

MANEUVRE MODE

Please keep in mind that this kind of spare power is not maintained during connection of „big consumers“! If spare power is sufficient with the spare-generator connected, the “big consumer” will be connected immediately and an additional generator-set will be started and connected later.

07.11.2010

DT, Dr. Horn

MANUAL MODE

With SW-versions 271.001020.H0 & H1 running generators in manual mode are included in the priority chain and may therefore tangle PMS & Blackout-start!

23.04.2010

DT, Dr. Horn

BAT500: New Designer-tool

Exor released version 6.07, which is available via Livelink/SAM-CMIS (online)/Enterprise Workspace/Products/Energy & Drives/Geapas 500/Software/BAT 500 Touch Screen Panel/BAT500 / Designtool (Designer 6) since 26.11.09.

Designer 6.04 is not able of programming flashcards with files, which are created by Designer 6.07!

From now on all new BAT500 software releases will be created using Designer 6.07, so please install 6.07 on all your computers!

16.06.2009

MBP5, Dr. Horn

IMPORTANT NOTICE: BusBar-numbers

Bus bar-numbers should be between 13 and 127 ($7F) because bit 7 has a special meaning! (1 to 12 may be used for generators automatically!)

11.06.2009

MBP5, Dr. Horn

Bug-fix: (271.001020.F4->F5)

Emergency-Stop-Signal in MODBUS not longer used with ordinary stops

15.10.2008

MBP5, Dr. Horn

Bug-fix: (271.001020.F1->F2)

- Synchronisation interlock covering all device numbers (“lowest number wins”)

Please remember: “Looser” continues synchronizing after connection of “winner”!

26.09.2008

MBP5, Dr. Horn

Bug-fixes: (271.001020.F0->F1)

- SG-DG interlock inhibited during "STOP" of SG

- "STOP" process finished after STOP pulse if cooldown time = 0

10.09.2008

MBP5, Dr. Horn

Bug-fixes: (E0->F0)

-Stop pulse can be cancelled by start command immediately (important for BO-start)

- Harbour Generator PMS corrected

- Trip of breakers after BusBarBlock enabled (e.g. tiebreakers to limit the affected area)

- Automatic BO-connection for tiebreakers from both sides allowed

ANSI 67N: (E2)

Directional Groundfault Function included, requires TRV504 and SLE-SW 271.001304

27.02.2008

MBP5, Dr. Horn

Harbour-mode:

271.001020.D9..E0 etc. contain a harbour mode mechanism:

  • Main generators are stopped after connection of harbour generator

  • Start of main generator requests stop of harbour generator, which will be executed after paralleling

Bit redefined in GPM-Bus, software should not be mingled with older versions.

05.02.2008

MBP5, Dr. Horn

Loadmonitor:

If all GPMs loadmonitors are inactive, no start passing will occur, because no generator can be started automatically

31.01.2008

MBP5, Dr. Horn

Emergency Generator:

Emergency generators may be paralleled to main generators for test purposes. In that case the GPM500 tries to load the generator with the amount of power defined in the TOPLOAD parameter (Par.175) provided that main generators are not underloaded. For automatic TOPLOAD limitation the underload prealarm limit (Par. 61) in the EG-GPM must be set accordingly.

If there is no GPM-Bus connection between emergency and main switchboard Par.61 nevertheless had to be set to zero to deactivate the TOPLOAD limitation mechanism. In that case operators must provide sufficient load before connecting the EG!

19.12.2007

MBP5, Dr. Horn

Important! Short-circuit trip-delay

Due to improved transformer-inrush-detection trip may be delayed for several seconds if second-order harmonics are detected.

To avoid problems and questions regarding the proper discrimination of faults Par. 94 (ANSI 87: Differential Protection (2.Harmonics [0.1%])) should be set to 99.9 % for standard applications!

10.12.2007

MBP5, Dr. Horn

GPM-Standard updated (271.001020.D6):

  • Bit 10 in “Short-circuit “-.Function codes sets BusBarBlock only if short-circuit occurs within 10 seconds after connection. That mechanism allows connection of another generator after short-circuit.

  • Diesel-Stop-output maintained until generator voltage is below 10 %


04.12.2007

MBP5, Dr. Horn

Description of Emergency-/Harbour Generator application using additional DIO500.

Document placed in Folder Geapas500/Documentation/GPM500/Application Notes

04.12.2007

MBP5, Dr. Horn

Geapas500/Documentation/GPM500/Application Notes created





3 / 3