Emergency Generator
GPM500 for EG are supporting additional functions compared with GPM for normal generators:
UNLOADING and STOP of EG is allowed without respect to its load if one of the transfer-line breakers is closed (indicated by DIO500#3:15 (DI7) or DIO500#3:16 (DI8) active)
TOPLOAD (asymmetrical loadsharing) is activated as long as DIO500#3:15 or DIO500#3:16 are active (transfer-line closed). So EG remains loaded as long as running in parallel with other GEN!
The GPM500 is able to synchronize the EG with the Emergency switchboard as well as the emergency switchboard with the transfer-line. The synchronizing request may be given using DI5 (DIO500#3:13) or DI6 (DIO500#3:12) . The synchronizing request should be activated only, if the mains voltage channel is connected to the repective transferline before. Please keep in mind that synchronization will be started either automatically (Bit 9 of Par. 147 set!) or must be started manually by touchbutton „Start“ or DIO500#1:9 (DI 1) (if Bit 8 of Par. 147 set!).