Function codes:
Protection functions actions may be parameterized to fit to the situation:
|
Bitposition / Mnemonic |
Description |
Value (hex) |
Value (dez) |
|
|---|---|---|---|---|
|
0 |
OP |
In OPeration: Protection function is activated. |
01 |
1 |
|
1 |
TR |
TRip: Breaker should trip in case of fault. |
02 |
2 |
|
2 |
DEX |
DEeXcitation: Generator should be deexcited in case of fault |
04 |
4 |
|
3 |
STP |
SToP: Stop engine |
08 |
8 |
|
4 |
LQ |
Lokal Quit: Alarm must be resetted by hardware input (local) |
10 |
16 |
|
5 |
SPR |
Start PRerogation: Another generator should be started, the affected generator to be disconnected at least 60 seconds after another generator is ready to synchronize. In case of successful synchronization the faulty generator will be unloaded and disconnected. It will observe the compulsory after-run/cool-down time. (Software versions 271.001004G , 271.001020B and higher: If a generators GPM is in MANUAL mode, the engine is stopped and disconnected immediately without starting another engine!) |
20 |
32 |
|
6 |
BL |
Block: Alarm must be resetted to cease trip command, deexcitation command etc. |
40 |
64 |
|
7 |
BBB |
BusBarBlock: No device should be switched on this busbar |
80 |
128 |