ANSI 50/51LR: Start block [0.1 s] Par. 100:

Asynchronous Motors may have very high initial currents. To prevent current-related protection functions (ANSI50: Instantaneous overcurrent / short circuit) from tripping, these protection functions can be blocked for a certain time interval after closing the breaker. This time can be set in steps of 100 ms: xxxx*0.1 s.

The trip delay of protection functions ANSI50 (Par.2 & Par.4) should be greater than 50 ms to leave time to detect the breaker-closed signal!

(See also ANSI 50 / Par.101 and ANSI 50 / Par.102)