ANSI 51N: Earthfault -Function (Par.124):
Bit 0-7 – GPM500´s action in case of earthfault may be defined here (ref. Function Codes).
(current limit ref. Par.47, tripping delay refer to Par.48)
Bit 8&9 – Ground-fault mode: GPM supports three different modes of ground-fault detection
|
Bit 9 |
Bit 8 |
ANSI-Code |
Description |
|
0 |
0 |
51N |
Ground over-current: Non-directional protection based on current through a dedicated current-transformer (ZCT) |
|
0 |
1 |
87N |
Ground-current differential-protection: Two ZCT wired together to detect internal faults only |
|
1 |
0 |
67N |
Directional ground-over-current: Current through ZCT is compared with displacement-voltage to determine whether the ground-fault is located inside or outside. (refer to Par.91) Normally the special TRV504 with high-gain channel is used for that purpose. |
|
1 |
1 |
spare |
-- |