ANSI 51N: Earthfault -Function (Par.124):

Bit 0-7 – GPM500´s action in case of earthfault may be defined here (ref. Function Codes).

(current limit ref. Par.47, tripping delay refer to Par.48)

Bit 8&9 – Ground-fault mode: GPM supports three different modes of ground-fault detection

Bit 9

Bit 8

ANSI-Code

Description

0

0

51N

Ground over-current: Non-directional protection based on current through a dedicated current-transformer (ZCT)

0

1

87N

Ground-current differential-protection: Two ZCT wired together to detect internal faults only

1

0

67N

Directional ground-over-current: Current through ZCT is compared with displacement-voltage to determine whether the ground-fault is located inside or outside. (refer to Par.91) Normally the special TRV504 with high-gain channel is used for that purpose.

1

1

spare

--




uh,14/02/12,13:28:56