Startfailure -Function(Par.143):
Low Byte:
A startfailure is detected, if breaker is not ready for synchronization within a certain time interval (defined in Par. 83) after start. GPM500´s action in case of startfailure has to be defined in the lower Byte (ref. Function Codes). It is required to define actions like TRIP, STOP, Start Passing SPR in case of startfailure to finish the start procedure and perform a 'hard' trip.
High Byte:
Normally a single start pulse of 8 s length is given to the diesel control unit. In special cases more start pulses may be required. Number of pulses during the time interval defined in Par. 83 may be defined in the high Byte of this parameter.