Stopfailure -Function(Par.144):
Lower Byte:
Stopfailure is detected, if
Breaker is not opened in a certain time interval (defined in Par. 84) after getting the STOP command
Generator voltage is not reduced below 10 % of rated voltage in a certain time interval (defined in Par. 84) after giving the STOP pulse to the diesel
GPM500´s action in case of stopfailure has to be defined in the lower Byte (ref. Function Codes). It is sometimes required to define actions like TRIP, STOP in case of stopfailure to finish the stop procedure and perform a 'hard' trip. This is often important with tiebreakers, which may not be unloaded totally because of insufficient spare power on one side!
Upper Byte:
Bit 8: Stop-failure alarm is triggered, if DG and shaft-generator (shore-connection) are running parallel
Bit 9: If set in addition to bit 8, the device in the stop-sequence will open it's breaker immediately to terminate parallel operation of DG and shaft-generator (shore-connection) !