Synchronization mode / Synchronization failure (Par.147):

Synchronization mode (High Byte):

Bit 8 & 9 – Three synchronization modes can be chosen :

Bit 10 – Use DIO500#3:14 as Diesel-running-information (if bit is not set, blackout-signal is taken instead)

Bit 11 – Thruster-mode possible: Generator uses second breaker to feed thruster directly (DIO500#3:14 used to indicate that thruster-operation is selected, DIO500#3:16 used to indicate, that thruster-breaker is closed ( DIO500#1:10 must be closed in addition!) (DIO500#3:13/15 may be used in the same way)

Bit 12 – Pre-magnetization of a transformer (usually engine-room-transformer) after blackout by de-excitation of the first connected generator, connection of the transformer and finally re-excitation! Bit must be set with the transformer and the generators!

Bit 13 – Additional SYNC-condition: DIO500#3:13 must be activate to synchronize or make a blackout-connection. Used e.g. for monitoring a pre-magnetization device!

Bit 14 – Ring-synchronization mode: The start-relay (DIO500#1:DO1) may generally be used to activate pre-magnetization devices before connection. In special cases the relay should only be activated, if the network is a ring: E.g. one engine-room transformer supplying the pre-magnetization device of the other transformer.

Remark: A ring-synchronisation is assumed, if voltage-difference, frequency-difference and angle are in the limits for more than 4 seconds, which will normally only be the case, if the compared voltages are derived from the sam source.

Bit 15 – OFF / TRIP separated: Normally the output SLE50x:7,8 is used for trip in case of fault and for normal disconnection. That makes sure, that the output and it's connection is regularly tested. In special cases OFF can be routed to the OperationMode-DIO:DO4 or the PreferentialTrip-DIO:DO4, while trip-signal remains routed to the SLE!

Synchronization failure (Low Byte):

GPM500´s action in case of sync failure has to be defined in the lower Byte (Bit 0 – 7) (ref. Function Codes). (Synchronization time ref. Par. 87)


uh,14/02/12,11:58:52