Breaker failure (Par. 148):
GPM500 evaluates different feedback signals regarding breaker position, position of the earthing contactor etc. Following pairs of signals may be monitored:
|
Signal 1 |
Input contact |
Signal 2 |
Input contact |
Signal 2 evaluated, if Bit x set ... |
|---|---|---|---|---|
|
Breaker closed |
DIO500#1:10 |
Breaker open |
DIO500#2:14 |
Par.148, Bit 10 (“INV”) |
|
Breaker in isolated position (drawn out) |
DIO500#2:11 |
Breaker in operational position (inserted) |
DIO500#2:10 |
Par.148, Bit. 8 (“TRE”) |
|
Earthing contactor closed |
DIO500#2:12 |
Earthing contactor open |
DIO500#2:13 |
Par.148, Bit. 9 (“ERD”) |
|
Control tripcoil |
SLE500:7,8 |
Input tripcoil monitoring |
SLE500:14 |
Par.148, Bit. 11 (“COIL”) |
|
Set position Breaker CB |
EKGEISOLL (internal signal) |
Breaker closed |
DIO500#1:10 |
ever |
|
Set position closing coil |
TRUE, wound up |
Breaker ready |
DIO500#2:9 |
ever |
Breaker and contactor positions are displayed as follows:

GPM 500 provides no special signal for winding up the breakers closing coil. It is assumed, that breakers are winding up automatically after closing. Nevertheless GPM500 monitors whether the closing coil is tensioned (Be aware, that neither diesel will be started nor circuit breaker closed without!):
|
Status |
Indication |
Remark |
|---|---|---|
|
Closing spring charged, Breaker ready |
|
DIO500#2:9 on +24V internal |
|
Coil relaxed, breaker not ready |
|
DIO500#2:9 open
|
Action in case of alarm must be defined here by use of Function Codes.