Breaker failure (Par. 148):

GPM500 evaluates different feedback signals regarding breaker position, position of the earthing contactor etc. Following pairs of signals may be monitored:

 

Signal 1

Input contact

Signal 2

Input contact

Signal 2 evaluated, if Bit x set ...

Breaker closed

DIO500#1:10

Breaker open

DIO500#2:14

Par.148, Bit 10

(“INV”)

Breaker in isolated position

(drawn out)

DIO500#2:11

Breaker in operational position

(inserted)

DIO500#2:10

Par.148, Bit. 8

(“TRE”)

Earthing contactor closed

DIO500#2:12

Earthing contactor open

DIO500#2:13

Par.148, Bit. 9

(“ERD”)

Control tripcoil

SLE500:7,8

Input tripcoil monitoring

SLE500:14

Par.148, Bit. 11

(“COIL”)

Set position Breaker CB

EKGEISOLL (internal signal)

Breaker closed

DIO500#1:10

ever

Set position closing coil

TRUE, wound up

Breaker ready

DIO500#2:9

ever

 

Breaker and contactor positions are displayed as follows:






 

GPM 500 provides no special signal for winding up the breakers closing coil. It is assumed, that breakers are winding up automatically after closing. Nevertheless GPM500 monitors whether the closing coil is tensioned (Be aware, that neither diesel will be started nor circuit breaker closed without!):

  

Status

Indication

Remark

Closing spring charged, Breaker   ready



DIO500#2:9 on +24V internal

Coil relaxed, breaker not ready


FLASHING

DIO500#2:9 open

 



 

Action in case of alarm must be defined here by use of Function Codes.