CAN4 failure (Par. 154):
CAN4 connects the GPM500 with external devices like the Touchpanel BAT500. Communication on this bus follows the CANopen standard. "CAN4 failure"; arises with faulty or missing external devices as well as with "Warning"; and "Bus-OFF" - messages from the CAN-Controller.
High Byte
Bit 8: Establishes communication with panel with COB-Id 3 (PDO-Identifier $183 / $203)
Bit 9: Establishes communication with panel with COB-Id 4 (PDO-Identifier $184 / $204)
Bit 10: Establishes communication with panel with COB-Id 5 (PDO-Identifier $185 / $205)
Bit 12: Establishes communication with Diesel Protection Module DPM COB-Id 01 ($01, PDO-Identifier $181 / $201)
Bit 15: Normally Panels are interlocked against each other, TAKE & REL(ease)-buttons are needed to take and release control for a certain panel. Set Bit 15 to allow permanent, parallel access for all panels.
Low Byte
Action in case of alarm must be defined here by use of Function Codes.