Load distribution: Amplification Synchronizing control [%] (Par.192):

Amplification is to be defined in percent : xxxx %

This value describes the influence of frequency deviations on the controller before connnection, while Par.170 handles frequency deviations after connection. The synchronization controller is nevertheless limited to values given in Par.23, Par.25, Par.27 and Par.29 to avoid synchronizing with an over- or underfrequent busbar. This applies also in case of disabled alarms!