Start priority (Par.199):
Priorities of gensets are build using the following scheme (priority doubleword):
|
Byte |
3 |
2 |
1 |
0 |
||
|---|---|---|---|---|---|---|
|
Content |
Special |
Par.199 |
Operation Hours Equivalent [h] |
Gen. No |
||
The genset with the lowest priority is started first and stopped last. The components of the priority word sorted by their effect:
The influence of special bits on the start and stop order is most important. A genset, which is still cooling down, will be reconnected first for example.
Priority settings from the operator (Par. 199) overrule automatic mechanisms
Normally the GPM´s try to manage start & stop using the respective operating hours, whereas the genset with the lowest number of hours will be started first and stopped last.
If all other mechanisms fail, the device numbers are compared.
Only gensets are taken into account, whose individual start and stop limits are met. That may have the effect, that a smaller generator is started or stopped before a larger one with better priority. A smaller generator may be ignored, if a larger one is able to
ZKG 500: Par.193-200 may only be changed via touchpanel or by the process itself, they can not be influenced by parameter download!
ZKG501: Par.193-200 are included in the parameter download!