ANSI 40: Field Failure (Par.55)
The reactive power limit („Underexcitation“) had to be defined in percent of the apparent power of the generator: xxx % . Trip delay is defined in Par.56, the action in case of alarm has to be defined in Par.128.
A negative value can be used to use the field failure alarm for monitoring asynchronous motors during starting up. If blocked, the motor will take too much reactive power. During a normal start the reactive load will be reduced quickly.