ANSI 51: Overcurrent, inverse time PREALARM (Par.82)
Tripping delay (ttrip) of this protection function is current-dependent according to the following („very inverse“) characteristic (with maximum phase-current I and rated current Irated):

Par.82 defines factor K in xxxx * 10 ms, reaction of the function must be defined in Parameter 142. We achieve the following characteristic: (Rectangles with equal energy!)

Please
take in mind, that alarm is active unless the heat integral
is
again below the value given here.