Synchronization time START PASSING [0.01 s] (Par. 90):

In case of START PASSING, the calling GPM (the GPM protecting the faulty generator/diesel) will allow synchronizing the standby genset for xxx s after stand-by set reaching the switch-on release (Par.185). If no synchronization is possible, the faulty genset will be disconnected and stopped to allow a blackout-connection of the standby-set!