ANSI 67N: Direction / Down 3 No. (Par. 91):
Low Byte –
Generators (especially Shaft Generators) may be connected to several busbars. The actual DOWN busbar may be selected by using Digital Inputs on DIO500#3. Par.91 (low Byte) describes the assigned busbar in case DIO500#3:15 (DI7) is activated.
Overview
UP is the busbar number of the logical busbar which is source of power (three-phase voltage measuring), while ...
DOWN (DOWN 2, DOWN 3) are the busbar numbers of the logical busbars which are consumer (two-phase voltage measuring)! One of the busbar numbers is selected as the actual down busbar via digital inputs:
|
|
Function for GEN |
Enabled by activating DI x of DIO500#3 |
Function for other devices |
Enabled by activating DI x of DIO500#3 |
|---|---|---|---|---|
|
Par.161 (High Byte) |
Device No. = UP |
-- |
Device No. |
-- |
|
Par.162 (High Byte) |
DOWN 2 |
8 (:16) |
UP |
-- |
|
Par.162 (Low Byte) |
DOWN |
no |
DOWN |
-- |
|
Par.91 (Low Byte) |
DOWN 3 |
7 (:15) AND NOT 8 (:16) |
DOWN 3 |
7 (:15) AND NOT 8 (:16) |
High Byte – α [11.25°]
the Directional Ground-fault protection needs to define a tripping- and a blocking-area regarding the angle between displacement-voltage and ground-current. The value is given in steps of 11.25°.