Preferential Trip (51/81L):

The GPM500 provides 5 steps of preferential tripping for consumers in case of generator overload. Every step can be activated by a frequency treshold as well as a current treshold. The steps are defined by 3 values each:

  1. Current threshold value (Reg.37), Frequency treshold value (Par.38) & Tripping Delay (Par.119)

  2. Current threshold value (Reg.39), Frequency treshold value (Par.40) & Tripping Delay (Par.120)

  3. Current threshold value (Reg.41), Frequency treshold value (Par.42) & Tripping Delay (Par.121),

  4. Current threshold value (Reg.43), Frequency treshold value (Par.44) & Tripping Delay (Par.122),

  5. Current threshold value (Reg.45), Frequency treshold value (Par.46) & Tripping Delay (Par.123),