Priority:

Automatic starting or stopping of generators requires definition of an order. Any GPM500 gets an priority number assigned, the GPM500 with the lowest number acts next.

The priority number is not a parameter, but must be (re-)assigned after power-on. Priority number includes the unique device number (Par.161) in the low byte to avoid collisions in case of equal priority numbers. Generators priority number is temporarily increased to 255, if generator was connected last, to avoid repeated connection and disconnection of one breaker.


UH, 29.10.04, 10:10:10