Subnet Number:

Subnet number is calculated according to the following scheme:

  1. Subnet number is the lowest Device. No. (Par.161) carried by any of the generators feeding this subnet. A Subnet No. is assigned to every device.

  2. Subnet No. is only influenced by closed switching devices.

  3. Closed tiebreakers and coupling devices transfer Subnet Numbers

  4. Open tiebreakers and coupling devices carry Subnet Number 250

  5. Closed loops are (normally) forbidden1


The drawing shows a network of three busbars with three operating generators and the calculated subnet numbers.


UH,17.10.04,16:20:45

1Closed loops may store subnet numbers resulting from meanwhile disconnected generators. Ask SAM for details.