Voltage Restrained Overcurrent (Par.100 and 101)



Rated currents of consumers may often be higher than rated currents of (small) generators.

In that case short-circuit trip limit may be reduced dynamically according to the remaining voltage:

Between rated voltage and 20 % of rated voltage the trip limit is proportional to the remaining voltage.

That means, instantaneous over-current (short circuit) protection is replaced by an „underimpedance“

protection and is so independent from number and size of generators connected!