ANSI 51: Preferential Trip Extension / Overcurrent, definite time (Parameter 104):
Bit 15
The third DIO500 (DIO500#3) will be provide additional features, if Bit 15 is set:
two additional steps of preferential trip:
DO 1 (DIO500#3:5,6) – Step 4
DO 4 (DIO500#3:3,4) may be used to control a lockout relay.
DI 8 (DIO500#3:16) is used for selection of the appropriate busbar for a generator, which may be connected to two different busbars. Par. 161 (Upper Byte) is used as busbar No. if input is set, Par. 162 (Upper Byte) is used, if input is open. (Refer to DIO500.htm)
Low Byte
Several actions may be defined (ref.Function Codes ). (current limit ref. Par.7, tripping delay refer to Par.8)