DIO500:
The GPM500 may be equipped with 2-7 Digital Input Output units (DIO500). The DIO500 bear each 8 inputs and 4 outputs, whereas two inputs may be coupled to form a fail-safe input. Function of any DIO500 is influenced as well by its ordinal number as by parameters. DIO500#1 and DIO500#2 have standardized functions, DIO 3 –7 may have different functions:
PREFerential TRIP: Two additional steps of preferential trip, selection of busbar number via DI8, lockout relay via DO 4
Operation MODE SELection: Selection and feedback of operation modes NO DG STOP (DI 2 / DO 2), NO DG START (DI 1 / DO 1) and MANUVRE MODE (DI 3 / DO 3), selection of busbar number via DI7/DI8 and lockout relay via DO 4
Consumer Control: Up to three DIO may be used to control large consumers, two consumer per DIO. DI8 of DIO500#3 for selection of busbar number.
Special Function DIO 1 & 2: Special project-specific functions may be implemented and may use additional DIO500
We obtain the following scheme:
|
Par: |
DIO#x |
|||||||
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
||
|
0 |
0 |
Standard |
Consumer Control |
- undefined - |
||||
|
0 |
1 |
MODE SEL |
Consumer Control |
- undef- |
||||
|
1 |
0 |
PREF TRIP |
Consumer Control |
- undef- |
||||
|
1 |
1 |
PREF TRIP |
MODE SEL |
Consumer Control |
||||
The third DIO (DIO500#3) bears some standard inputs, which are available as well on DIO500 for PREFerential TRIP, Operation MODE SELection and Consumer Control:
DIO500#3:13 (DI5): Synchronization request Transferline 2
DIO500#3:14 (DI6): Synchronization request Transferline 1
DIO500#3:15 (DI7): Transferline 2 closed / device (generator or transformer) is connected to busbar No. Par.91 DOWN 3
DIO500#3:15 (DI7): Transferline 1 closed / generator is connected to busbar No. Par.162 (High Byte / DOWN 2)