Manuvre Mode:
GPM500 provides automatic START and STOP of generators depending from actual and requested load of consumers.
The GPM Power Management optimizes the number of working generator sets. Sometimes it is required to have one „spare“ generator running with the others. If „Manuvre Mode“ is choosen for one generator set, the rated power of this respective generator will be added to the requested spare power.
„Manuvre Mode“ may either be choosen by connecting a digital input at the third DIO500 (DI 3) or via Modbus. If „Manuvre Mode“ is selected, output relay DO3 of the third DIO500 will be activated for GPM500 belonging to the respective subnet.