Up No. / Down No. (Par.162):
Any breaker is connecting two different electrical systems (which should be named busbar, without paying respect to their physical nature). So its place in the network topology may be fully described by numbers assigned to these “busbars“;. These unique numbers should be quoted as Busbar No.s.
Up No. (High Byte):
Busbar No. of the producer (upstream)
Down No. (Low Byte):
Busbar No. of the consumer (downstream)
For GENERATORS Down No. refers to the standard busbar, while Up No. refers to a second busbar. Digital Input DI8 of the third DIO500 may be used to inform the GPM about the selected busbar. In fact, the upstream Busbar No. of the generator is in any case the Generator No. / Device No. , so no special definition of that number is required (Refer to. Parameter161.htm). DI 7 may be used to select the busbar No. given in Parameter 91!
Overview
UP is the busbar number of the logical busbar which is source of power (three-phase voltage measuring), while ...
DOWN (DOWN 2, DOWN 3) are the busbar numbers of the logical busbars which are consumer (two-phase voltage measuring)! One of the busbar numbers is selected as the actual down busbar via digital inputs:
|
|
Function for GEN |
Enabled by activating DI x of DIO500#3 |
Function for other devices |
Enabled by activating DI x of DIO500#3 |
|---|---|---|---|---|
|
Par.161 (High Byte) |
Device No. = UP |
-- |
Device No. |
-- |
|
Par.162 (High Byte) |
DOWN 2 |
8 (:16) |
UP |
-- |
|
Par.162 (Low Byte) |
DOWN |
no |
DOWN |
-- |
|
Par.91 (Low Byte) |
DOWN 3 |
7 (:15) AND NOT 8 (:16) |
DOWN 3 |
7 (:15) AND NOT 8 (:16) |