Governormotor failure -Function (Par. 140):
A generator-set may not reach the set-frequency and or the requested share of load. There are several reasons for that:
missing supply voltage for governor-motor
defunct governor (wrong limits, wiring)
insufficient fuel supply for prime mover (fuel filter)
configuration errors
An alarm is given, if the GPM500 is giving consecutive UP/DOWN (Increase speed/Decrease speed) signal for three minutes or more!
Action must be defined here by use of Function Codes.