Voltage-NEG1 (Par. 149):

GPM500 is designed for use with two independent supply voltages:

  1. AC 3~,19 V: NEG50x:5,6,7 Generator voltage via transformer (Voltage-NEG1)

  2. DC 24 V: NEG50x:1,4 Automation battery (Voltage-NEG2)

The Voltage-NEG1 alarm is only active if lowest generator voltage is greater than the release-voltage (Par.185)

The AC input may also be used for an second independent DC supply. ( NEG50x:5,6,7 – 24 V, NEG50x:3,4 – 0 V). In that case Bit 8 should be set in addition to the common Function Codes to get the alarm independent from the actual generator voltage!

Action in case of alarm must be defined here by use of Function Codes.