Rated Voltage (Par.160):
Rated voltage had to be defined in Par 160: xxxxx V. If differential Protection is used, rated voltages for other coil systems must be defined: Secondary coil 1 (Par. 179) and Secondary coil 2 (Par. 180). These voltages must also be defined for generators, where Par.160=Par.179.
With GENERATORS it is very important, to define the rated voltage of secondary coil 1 equal to the rated voltage of the generator to avoid erraneous tripping! Try to think about generators as transformers with ratio 1:1!