Rated Voltage Secondary coil 1(Par.179):
Rated voltage had to be defined in Par 179: xxxxx V. (Refer to Par.160 and Par.180)
Transformation ratios are automatically calculated from primary rated voltage (Par. 160) and the rated secondary voltages (Par.180). Rated secondary voltages should be lower than the primary voltage and should be calculated by using the exact transformation ratio (should not include voltage drop!). One rated voltage should be defined for each group of current transformers:
Transformers may have two or three coil systems, two or three groups of current transformers and may therefore have two or three rated voltages
Generators may have just one coil system, but one or two current transformer groups, therefore one or two rated voltages.
Rated secondary voltage should be set zero for missing current transformer groups.
With GENERATORS WITH differential protection (ANSI 87) it is very important, to define the rated voltage of secondary coil 1 equal to the rated voltage of the generator (Par.160 ) to avoid erraneous tripping! Try to think about generators as transformers with ratio 1:1!