Differential Protection (ANSI 87):

Differential Protection is a comparative protection mechanism: Difference between „IN“ and „OUT“- currents is calculated, breaker will be tripped, if this difference exceeds a given limit. Protection is restricted to the zone between „IN“- and „OUT“ current transformers:






Protection function 87 trips without delay, it must not be included in any selective tripping schedule. A tripping characteristic had to be used to prevent the protection device from tripping in case of an external fault (outside the Protection Zone ) . Parameter assignment for 87 may be complex, if the tripping characteristic had to be defined. Normally, there is no need to change the standard assignment.

The magnetizing inrush of transformers may cause trip by as well Overcurrent (ANSI 50, ANSI 51) protection as Differential protection. Inrush current can be identified by its strong second-order-harmonic. Tripping can be blocked in case of such harmonics, that mechanism is called Inrush Stabilization (Par. 94).

Transformers may cause a phase shift between primary and secondary currents. Several factors (Par.177, Par.178, Par. 179 & Par. 180) make primary and secondary currents comparable.

Remark: The differential protection system is designed to monitor three groups of coils. If only two groups are used (e.g. generators), the respective voltage parameter (Par. 179 & Par. 180) should be set kept zero!