Displacement angle Secondary coil 1 (Par.177):

Transformers secondary voltages may not be in phase to primary voltages, the angle between secondary and primary voltage must be given in 0.1 degrees: xxxx*0.1°

GPM500 may monitor transformers bearing three systems of windings, so a second displacement angle may be defined in Par.178.

Setting of displacement angles (Par.177-178) is mandatory, if using Differential Protection. (also for generators using 0.0° or 180.0°)

Transformation ratios are automatically calculated from primary rated voltage (Par. 160) and the rated secondary voltages (Par. 179 & Par.180). Rated secondary voltages should be lower than the primary voltage and should be calculated by using the exact transformation ratio (should not include voltage drop!).