Tripping Characteristic (Differential Protection, ANSI 87):
The protection device GPM500 uses the following tripping characteristic to prevent the protection funtion 87 from erraneous tripping:

Current
transformers accuracy will become lower with increasing currents, so
the protection device may trip without having a real current
difference. The tolerable current difference Idiff had to
be increased with increasing „through“-current Istab
to take into account the current transformers accuracy. This
mechanism is known as stabilization.
The tripping characteristic is build up by three straight lines defined by:
ku (Parameter 95): Minimum current difference
a1 (Parameter 96), v1 (Parameter 97) : line equation 1
a2 (Parameter 98), v2 (Parameter 99) : line equation 2
Function in case of alarm can be defined by using Par. 132 (ref. Function Codes)