Load limit [0.1 %] (Par.198):
A load limit may be used to reduce generators rated power after repair or in case of problems with the prime mover or if prime movers are not capable of delivering their rated power for a longer time. The load limit will be overruled in case of pending spare power requests for big consumers.
It may also be used to reduce the requested load in case of TOPLOAD (asymmetric loadsharing!). Initial setting for TOPLOAD may be defined using Parameter175.htm . TOPLOAD operation may also be implemented by an external Power Management System PMS by changing the settings of Par.198 for several generators.
Par.193-200 may only be changed via touchpanel or by the process itself, they can not be influenced by parameter download!