Load distribution: Topload [0.1 %] (Par.175):

Generator sets may be required to be loaded periodically to almost full power to keep the diesel engine performant. For this purpose the TOPLOAD mode may be choosen for one generator set per subnet. Mode is automatically activated for Emergency Generators running in parallel to mains! In this case the underload PREALAM limit should be set to zero (Par. 61), which is normally preventing the TOPLOAD generator from underloading the other generator sets!

The required level of load for this engine may be defined in percent of rated power by using this parameter! This setting may be altered using MODBUS command!


uh,14.06.07,10:13:07