ANSI 37: Underload PREALARM (Par.61)

The power limit („Underload“) had to be defined in percent of the rated power (Par.164) : xxx % . Trip delay is defined in Par.62, the action in case of alarm has to be defined in Par.131. The alarm is inhibited for generators in single mode.

This parameter is also used to define, how much load should be left to the other generator sets in case of TOPLOAD operation (Refer to Par.175). Par. 61 should be set to zero for emergency generators without CAN-connection to main-generators!