Startfailure [s](Par. 83):
Start of an generator set is monitored, if this protection function is activated. A voltage of about 80 % rated voltage (switch-on release, Par.185)must be reached in xxx s, otherwise an alarm occurs. Action in case of alarm must be defined in Parameter 143. It is required to define actions like TRIP, STOP, START PREROGATION in case of start failure to finish the start procedure and to allow the power management to start another generator.