Synchronization failure (Par. 87):

Synchronization of a generator set is monitored, if this protection function is activated. After voltage of about 80 % rated voltage (switch-on release, Par.185)is reached, generator breaker must be closed after xxx s, otherwise an alarm occurs. Action in case of alarm must be defined in Parameter 147.