Blackout Interlock:
Blackout is assumed, if two conditions are met:
Mains voltage Umains12 < 10 % rated voltage
Digital input DIO500(2):16 is set by a blackout relay
The use of two conditions is mandatory, because unsynchronized connection of a generator may as well harm the generator as cause a power supply breakdown. A blackout interlock may be simply realized by checking, whether all generator breakers (and tiebreakers etc. )are OPEN:

Blackout connections of two generators at the same time should be ruled out by further interlocks.