TRV500 (Isolation Amplifier):
The purpose of the TRV500 is the isolated voltage acquisition in GPM500 systems.
It replaces the voltage transformers having been used so far. Compared to them the TRV500 has the advantage of a smaller volume and less weight. The TRV500 is equipped with 3 measuring channels which, as standard, are configured as voltage inputs. The TRV500 can also be used for current measuring by using shunt resistors.
Up to now three different types of TRV are supported:
|
Type |
Description |
Max. Input |
|---|---|---|
|
TRV500 |
standard for 440 V networks (direct connection) |
All channels: 600 Vrms (848.528 Vpeak) |
|
TRV501 |
standard for medium voltage networks (voltage transformer secondary voltage standardized to 100 Vrms) |
All channels: 200 Vrms (282.84 Vpeak) |
|
TRV502 |
Channel 1 & 2 (TRV502:9,13 & 12,16) used for voltage acquisition via transformer, channel 3 (TRV502: 5,8) is used for metering ground currents. |
Channel 1 & 2: 200 Vrms (282.84 Vpeak) Channel 3: 1 Arms (1.4142 Apeak) |
TRV type must be selected in Parameter 188 . Two TRV may be selected for one GPM500. Please take into account, that displacement voltage muss be measured using channel „us1“ (SLE500:17) of the SLE500, while ground currents must be measured using „us2“(SLE500:18). It is recommended to make an external connection between the TRV502s outputs and SLE500 s inputs as needed:
|
Ext. No. |
Int. No. |
Assignment on TRV50x |
|
1 |
X3.4 |
Analog output of channel 1 |
|
2 |
X3.3 |
Analog output of channel 2d |
|
3 |
X3.2 |
Analog output of channel 3 |
Please set the respective jumpers in that case according to the following table:
|
J10 |
Connects channel 1 to X3.2 (terminal 3) |
|
J11 |
Connects channel 2 to X3.3 (terminal 2) |
|
J12 |
Connects channel 3 to X3.4 (terminal 1) |