Blackout Start (Par. 190):
Some generator sets should be started automatically in case of blackout (Blackout is defined by Umains12 < 10 % rated voltage AND DIO500(2):16 is set by blackout interlock(+24 V) ).
Start delay must be defined in steps of 100 ms : xxxx*0.1 s!
Blackout start is enabled by setting Par.189/Bit 0!