Stop condition [kW] (Par.67):

Generator set is started, if Total Spare Power TSP is above value xxxxx kW + generators rated power for time defined in Par.68 [0.1 seconds]. Loadmonitor must be activated by setting Par.189, Bit 1.

Stop limit may be set to negative values to allow use with an external Power Management System but GPM-internal load-distribution. So GPM500 will not check the available spare power but will still have the benefit of smooth unloading before disconnection!