Loadmonitor:
GPM500 provides automatic START and STOP of generators depending from actual and requested load of consumers. This function can be activated in any GPM500 and is distributed over several GPM500 (this is an important part of Power Management!). Load monitoring requires several steps:
Any GPM500 calculates the spare power requested by its consumers.
This spare power request is sent via CAN1 & CAN2
Any generators GPM500 calculates the spare power requested for consumers belonging to its subnet.
GPM500 of generators check, whether total spare power (TSP) requires START or STOP of a generator
Generators GPM500 are comparing their own priority with the priority of others and decide whether to START or STOP .
Two start conditions and one stop condition must be evaluated:
Start and stop conditions are defined as absolute power values (kW), conditions for apparent power (kVA) are derived from these settings automatically. These conditions are purely seen from an electrotechnical point of view: A safe power supply should be maintained. The GPM500 loadmonitor assumes, that generators and engines may be loaded 100%. If an operation near 100% is not appropriate permanently, the diesel power should be restricted by using Par.198 (to be set via touchscreen or MODBUS only, not with the PARA1-tool)!
If start or stop conditions are fullfilled for more than one generator, the generator with highest priority will be connected/disconnected. Conditions for generators may be different, if generators rated powers are not equal: Condition for a small generator may be fulfilled before conditions for larger generators are met. So efficiency of the system may be improved.