Power Management:
The GPM500 provides several power management functions although initially designed as a pure protection device:
Synchroncheck
Synchronizing of generators and subnets. Any GPM500 contains a synchronizing regulator which operates either „UP“- and „DOWN“ outputs of the GOV500 or uses a telegram via CAN1 and CAN 2 which influences „UP“- and „DOWN“ outputs of other GPM500. This telegram contains two subnet codes, it effect is restricted to these subnets.
Powersharing between generators belonging to one subnet .
Unloading generators and busties before opening the respective breaker. The GPM500 operates either „UP“- and „DOWN“ outputs of its GOV500 or uses a telegram via CAN1 and CAN 2 which influences „UP“- and „DOWN“ outputs of other GPM500. This telegram contains two subnet codes, its effect is restricted to these subnets.
Reserving spare power for certain consumers (Load monitor!). Spare power is calculated for any subnet separately. Any GPM500 is building up a cumulated sum of spare power requested by the consumers controlled by this GPM500. The generators own rated power is requested (in addition), as long as Manuvre Mode is selected for that respective generator.
Starting and stopping of generator sets according to the requested/available spare power! A startpriority may be assigned to generators by the operator, initial startpriority is equal to generator number.
The power management functions are distributed among the GPM500 to obtain flexibility, especially the load monitor function is divided in more or less independent parts:
Any GPM500 (whether protecting a generator, motor etc.) may generate a spare power request for the device protected and/or for additional devices.
Generators GPM500 are calculating actual spare power as well as requested spare power for their subnet and compare these results with their individual start and stop limits.
Generators GPM500 check, whether they have got the highest startpriority, and start/stop their gensets in that case.