Voltage
channel failure -Function (Par. 139):
Generators: Three conditions are used to
determine, whether the main busbar is free of voltage:
· Mains voltage Umains12 < 10 % rated voltage
·
Digital input DIO500(2):16 is set by a blackout relay
·
Number of Generators connected to the respective subnet is zero
(via GPM-Bus)
The
signals are compared to each other to detect the failure of an individual
signal. It is nevertheless not forbidden to have the zero generator condition met and the other conditions not. This
allows feeding of the busbar via shore connection etc.
Tiebreaker: Two conditions are used to
determine, whether one of the busbars is free of voltage:
·
Busbar voltage Umains12 < 10 % rated voltage or maximum of
busbar voltages Ugen12 ,Ugen12 < 10 % rated voltage
·
Digital input DIO500(2):16 is set by a blackout relay
(which indicates, that at least one side is free of voltage)
Both signals
are compared to each other to detect the failure of an individual signal.
Low
Byte: Action must be defined here by use of Function Codes.