Synchronizing:
Generators or networks must be synchronized to each other before closing the connecting breaker. GPM500 checks 2 conditions before synchronizing:
Network-/Generator voltages and frequency must be greater than the percentage set as release-voltage (Par. 185)!
Positive sequence voltage must be greater release-voltage (Par. 185)!
Four sychronization conditions must become true before closing the breaker:
Phase angle (Umains12 – Ugen12) must be lower than set in Par.181
Voltage difference must be smaller than defined in Par.182
Frequency difference must be below value in Par.183
Levitation voltage (Umains12 – Ugen12) must be lower than value in Par.184
Synchronizing time can be monitored (ref. Par.87 & Par.147/Byte0)!
Synchronization mode can be set to three modes (ref. Par.147/Byte1 )
0 („-0-“): No synchronization by GPM500 (Breaker will never be closed by GPM500)
1 („MAN“): GPM500 will connect after „START COMMAND“
2 („AUT“): GPM500 will try to connect if preconditions ( release-voltage (Par. 185) ) are fulfilled.
Anyhow selector switch (HAND/AUTO, DIO500(1):13) must be set to AUTO, to enable as well automatic synchronization as blackout connection.
Blackout connection may be allowed, if at least one side of the breaker is free of voltage. Two different cases and conditions must be considered:
Blackout 1: Vmains12 < 10 % Vrated AND Digital input DIO500(2):16 is set (See Blackout Interlock)
Blackout 2: Vgen12 < 10 % AND Vgen23 < 10 % AND Vgen31 < 10 % Vrated
Behaviour of the GPM500 is determined by the device type (Par.161):
Generators (Type 0 – 3): Blackout connection only in case 1
Tiebreakers, Transformers, Shore connections (Type 4 – 10) in case 1 or 2
Motors, Filters etc. (Type 11-15) only in case 1.
It should be kept in mind, that Vgen12, Vgen23 & Vgen31 are busbar voltages in case of consumers, while consumer voltage is normally not measured. Connection of a consumer is always an blackout connection and requires Digital input DIO500(2):16 to be set.